What is VLF Hipot Testing

VLF-60 KEP Product catalogue

KEP Product Catalogue

What is VLF Hipot Testing

Withstand or hipot testing is used to evaluate the condition of a cable insulation during installation, acceptance, or maintenance testing. As a result of a hipot test, at the point of an insulation defect an electrical tree will start to progress, create the insulation breakdown and make it possible for the technician to pinpoint the faulted place.

As a result of a hipot test, at the point of an insulation defect an electrical tree will start to progress, create the insulation breakdown and make it possible for the technician to pinpoint the faulted place.

The main focus of this article is the very low frequency (VLF) withstand cable test, which essentially is a type of AC hipot test conducted at a frequency rate of 0.01 to 1.00 Hz. Due to a significant drop in the operation frequency compared to AC hipot testing, done at 50 or 60 Hz, a VLF hipot tester is much smaller than a typical AC hipot test set, and thus is widely applicable for field usage.

Main VLF Hipot Testing Parameters: Waveform, Voltage, Duration

The typical waveforms for VLF testing include the sinewave, squarewave, and cosine-rectangular (trapezoidal) wave. The sinewave, or sinusoidal voltage, is the same as the voltage used by AC power systems. Out of the three mentioned waveforms, the sinewave is found to be the most efficient for cable testing as it causes the electrical tree to progress at the fastest rate, which results in shorter test times.

IEEE  400.2  guide stipulates that the test voltage should be 2.0 to 3.0 times the cables’ normal line to ground voltage. Since maintenance testing is done on service age cables, the recommended voltage is 80 per cent of that used for installation/acceptance testing. If there is a need to perform several test cycles, it may be reasonable to decrease the testing voltage by a further 20 per cent. The table below reflects the IEEE 400.2 guidelines as to the optimal testing sinewave voltage for 5 kV to 35 kV cables.

Table 1. VLF test voltage

Cable

rms voltage

Installation

rms / peak voltage

Acceptance

rms / peak voltage

Maintenance

rms / peak voltage

5 kV

9 / 13 kV

10 / 14 kV

7 / 10 kV

8 kV

11 / 16 kV

13 / 18 kV

10 / 14 kV

15 kV

18 / 25 kV

20 / 28 kV

16 / 22 kV

25 kV

27 / 38 kV

31 / 44 kV

23 / 33 kV

35 kV

39 / 55 kV

44 / 62 kV

33 / 47 kV


The advised testing time is 60 minutes at 0.1 Hz on new cables, and 30 minutes at 0.1 Hz on service age cables; it is recommended that the withstand testing time during maintenance testing should be extended to 60 minutes at 0.1 Hz if the circuit in question is of special importance.

VLF Testing Method

VLF testing is performed on offline cables, that is, the cable under test should be disconnected from the power system, and properly grounded. The VLF tester is then connected to the cable under test, and the required test voltage is set.

If the cable under test passes the VLF testing, the voltage should be decreased to zero, the cable under test and the VLF instrument should be discharged, and the cable should be grounded.
If the cable under test fails the test, the test voltage drops down to zero on its own. The VLF tester should be switched off for the cable and the tester to discharge, and the cable should be grounded. After that, the fault or faults can be found with fault locating instruments and repaired, or the respective cable sections are replaced.

VLF testing

Connection Setup for a VLF Cable


Advantages and Disadvantages of VLF Cable Testing

The strong points of VLF cable testing include the following:
  • VLF cable testing is applicable for extruded polyethylene, laminated paper, and mixed insulation;
  • the small size of the VLF test set is perfect for field testing;
  • VLF hipot testing can be done on both new and service age cables, which means that it can be used for installation, acceptance, and maintenance testing;
  • With the right voltage and testing time, VLF testing is not destructive for less severe insulation defects that could remain dormant for a long time and not impede the cable performance. Yet, it is efficient for locating more severe insulation defects that are likely to cause cable faults in the nearest future;
  • Combined with standard cable diagnostics equipment, the VLF test set can be used for diagnostic testing.
At the same time, the difficulties associated with VLF hipot testing are these:
  • VLF withstand testing may not provide conclusive results if the insulation is significantly damaged by water treeing or has partial discharges. In this situation, it is recommended that VLF testing should be combined with other diagnostic testing methods;
  • VLF testing with very high testing voltage at a frequency below 0.01 Hz may cause space charges in extruded polyethylene insulation;
  • VLF cable testing is done on offline cables only.
To sum up, although VLF withstand testing is attributed to destructive cable testing as it causes severe defects to initiate treeing and break down the insulation, the VLF test nevertheless does not harm good insulation. So, VLF hipot testing performed with alternating sinusoidal voltage best meets the testing purpose of locating and removing several defects in insulation that is mostly of good quality.



Alexei Tiatiushkin
Marketing manager
KharkovEnergoPribor Ltd.
marketing@keppowertesting.uk
http://www.kep.ua

http://news.chivindo.com/375/vlf-withstand-test-introduction-to-hipot-cable-testing.html

Comments

Popular posts from this blog

SketchUp Pro 2020 v20.1.235 Full Version

BAGAS31 – SketchUp Pro 2020 v20.1.235 Full Version  merupakan software yang dirancang untuk membantu sobat membuat dan mengedit model 3D. Dengan desain tampilan yang ‘clean’ dan simple, menjadikan software ini mudah untuk digunakan. Software ini hadir dengan editor bawaan yang memungkinkan sobat mendesain objek 3D dari awal, Layout designer untuk menggabungkan model 3D serta Style Builder untuk menyesuaikan model dengan gaya yang berbeda. Software ini juga memiliki fitur untuk mengimpor data dari format lain, seperti 3DS, DWG, KMZ, JPG, PNG, PSD, TIF, TGA dan sebagainya. Tanpa berpanjang lebar, silakan download  Sketch Up Pro  versi terbaru 2020 v20.1.235 Full Version   melalui link yang disediakan. SketchUp Pro 2020 v20.1.235 Full Version Screenshots : Download : SketchUp Pro 2020 v20.1.235 Installer | Size: 128 MB [ FileUp ] | [ up4ever ] JAMU SketchUp Pro 2020 v20.1.235 Full Version | Size: 14.5 MB [ FileUp ] | [ ...

Assembly ducting

Kode Konversi Digital

Angka dikodekan dalam bentuk lain, mewakili atau menggunakannya sesuai kebutuhan. Misalnya, Angka ‘Sembilan’ dikodekan dalam simbol Desimal (9)d, dalam Natural-Binary (1001)b. Komputer Digital berurusan bilangan biner. Metode mengkonversi kode dari satu format ke  format  lain  ➤ Biner ke BCD  (Binary Coded Decimal)  ➤ BCD ke Seven Segmen                       ➤  BCD ke Grey Code                              ➤  Grey Code ke BCD                              ➤ BCD ke  Excess-3                                ➤  Excess-3  ke BCD                ...

Skematik dan PCB Layout Rangkaian Adaptor (Power Supply) AC to DC output 5 Volt

Software Proteus 8 Professional merupakan salah satu software elektronik yang digunakan untuk membantu para designer dalam merancang dan mensimulasikan suatu rangkaian elektronik. Software ini memiliki dua fungsi sekaligus dalam satu paket, yaitu sebagai software untuk menggambar skematik dan digunakan sebagai merancang gambar Printed Circuit Board (PCB). Pada tulisan kali ini saya akan memberikan sedikit tutorial cara membuat rangkaian Adaptor (Power Supply) AC to DC untuk keluaran tegangan 5 volt. Aplikasi yang akan digunakan disini adalah Proteus 8 Profesional. Alasan saya menggunakan aplikasi ini karena inilah salah satu aplikasi paling popular digunakan para desainer. Selain itu aplikasi ini juga mudah didapat dan kompatibel dengan banyak platform. Sedangkan alasan saya mengangkat tema ini karena ini juga salah satu tugas mata kuliah saya di semester 4, yaitu mata kuliah Elektronika Dasar. Di mata kuliah ini banyak dijelaskan bagaimana membuat rangkaian elektronika dan praktik pem...

Studi Peralatan Pembangkit dan Penggerak Mula

Gangguan pada Pusat-pusat Listrik secara garis besar dapat dibagi atas 4 kelompok, yaitu : a. Gangguan pada sirkit listrik generator b. Gangguan pada mesin penggerak mula c. Gangguan pada instalasi yang berhubungan dengan lingkungan seperti instalasi air pendingin dan saluran air terbuka pada PLTA . d. Gangguan pada sirkit kontrol . Dalam instalasi yang dijaga oleh operator seperti Pusat Listrik dan Gardu Induk ada gangguan yang tidak atau belum dilihat oleh Relai , tapi dilihat oleh operator yang kemudian berinisiatif men-trip-kan atau membuka Pemutus Tenaga ( PMT )/ circuit breaker demi keselamatan instalasi , maka dalam hal ini operator bertindak sebagai relai. Gangguan pada Sirkit Listrik Generator yang menyebabkan tripnya PMT, pada umumnya disebabkan oleh : a. Gangguan diluar seksi generator tetapi PMT generator ikut trip sebagai akibat kurang selektifnya relai generator b. Ada gangguan dalam seksi generator yang disebabkan karena: " Kerusakan generator atau alat ...