There are several methods for the field testing of underground electric power cables which are grouped under the category of Type 1 Tests. These are intended to detect defects in the insulation of the cable system in order to improve the service reliability after the defective part is removed and appropriate repairs are performed. These tests are usually achieved by application of moderately increased voltage across the insulation for a prescribed duration of time. Such tests are categorized as a pass or fail, go or no go type of a test.

Type 1 Tests typically involve one of the following:

  1. the insulation resistance test performed with a standard megohmmeter, also known as undervoltage test; 
  2. the DC high potential test or DC hipot test;
  3. the very low frequency high potentials test (VLF hipot test); 
  4. the AC high potential test which is performed at power frequency (50 hertz or 60 hertz). 
It should be noted that due to the size of the equipment required for an AC hipot test on a very high capacitive device under test such as cable, normally the power frequency test is done at the factory, in cable labs, but is not used in the field.


Undervoltage tests utilizing DC voltage

Undervoltage tests are typically performed with megahometer. Since the test uses voltages under the rating of the insulation, the test is considered to be a nondestructive test and does not produce any of the harmful effects associated with a high voltage DC test. Insulation tests electrically stimulate the insulation and measure the response. Depending upon that response conclusions are drawn about the condition of the insulation.

What we need to know is that if perfect insulation existed, there would be no flow of electrical current through the insulation to ground. But since no insulation has infinite resistance, there is always some leakage current flowing through the insulation. While a small amount of current leaking through a good insulation is not a problem, difficulties arise when the insulation begins to deteriorate, and the leakage current begins to increase.

The insulation resistance test measures the resistance of the insulation material to the flow of the leakage current, helping to assess the condition of the insulation. This type of test allows either to measure the resistance or the flow of the leakage current.

Overvoltage testing utilizing DC voltage

For years high voltage DC testing has been a traditionally accepted method for judging the serviceability of MV cables. DC hipots or DC high potential tests have worked well as a withstand and condition assessment test for paper insulated led-covered PILC cables. When plastic insulation cables were first introduced, DC was still the preferred measurement method.

As time moved on, plastic insulated cables became more abundant and began showing aging effects and service aging. DC continued to be the dominant test, but concerns began to grow over the effectiveness of this test. Studies showed that while not causing any damage to new cables, DC hipot testing has a detrimental effect on service age cables on account of accelerating treeing effects.
high voltage insulation testing

Hipot Test Set HVTS-70/50


Currently, most standards continue to include DC testing as an acceptance test on newly installed extruded dielectrics, and almost all of the recommended practices have abandoned the use of DC testing for maintenance purposes, or particularly when the cable has reached service age (is over five years of age).

To locate a cable fault with DC hipot testing, the technician needs to find the point where current leaks through the faulted insulation, and for electricity to leak, it requires a conductive path.  In other words, two wires should be exposed, or there should be a wire and some other metal like the cable shield. So, in hipot testing, voltage is increased to cause leaking or arcing between exposed wires or cables, which helps to catch errors that otherwise would be missed.

Yet, there are a few reservations regarding dielectric failures that should be taken into account. It is possible for an insulation breach that results in a dielectric failure to self-heal, meaning that subsequent hipot test may actually pass. In addition, it is possible for small solder slivers which caused dielectric failures to be vaporized by the hipot test, meaning that subsequent hipot tests again may actually pass. It is also possible for these small solder slivers to leave a carbon track or be metallic sized when they are vaporized by the hipot test, meaning that subsequent hipot tests will fail. Because of these issues it is recommended that any cable that fails a hipot test be closely checked and retested at least twice.

To sum up, DC hipot testing is still widely applied for acceptance testing. Yet, when it comes to maintenance testing done in the field, VLF hipots are more commonly used, which will be discussed in more detail in the next article.

Alexei Tiatiushkin
Marketing manager
KharkovEnergoPribor Ltd.
marketing@keppowertesting.uk
http://news.chivindo.com/379/undervoltage-and-overvoltage-dc-testing-short-guide-to-hipot-tests.html

Comments

Popular posts from this blog

SketchUp Pro 2020 v20.1.235 Full Version

BAGAS31 – SketchUp Pro 2020 v20.1.235 Full Version  merupakan software yang dirancang untuk membantu sobat membuat dan mengedit model 3D. Dengan desain tampilan yang ‘clean’ dan simple, menjadikan software ini mudah untuk digunakan. Software ini hadir dengan editor bawaan yang memungkinkan sobat mendesain objek 3D dari awal, Layout designer untuk menggabungkan model 3D serta Style Builder untuk menyesuaikan model dengan gaya yang berbeda. Software ini juga memiliki fitur untuk mengimpor data dari format lain, seperti 3DS, DWG, KMZ, JPG, PNG, PSD, TIF, TGA dan sebagainya. Tanpa berpanjang lebar, silakan download  Sketch Up Pro  versi terbaru 2020 v20.1.235 Full Version   melalui link yang disediakan. SketchUp Pro 2020 v20.1.235 Full Version Screenshots : Download : SketchUp Pro 2020 v20.1.235 Installer | Size: 128 MB [ FileUp ] | [ up4ever ] JAMU SketchUp Pro 2020 v20.1.235 Full Version | Size: 14.5 MB [ FileUp ] | [ ...

Assembly ducting

Kode Konversi Digital

Angka dikodekan dalam bentuk lain, mewakili atau menggunakannya sesuai kebutuhan. Misalnya, Angka ‘Sembilan’ dikodekan dalam simbol Desimal (9)d, dalam Natural-Binary (1001)b. Komputer Digital berurusan bilangan biner. Metode mengkonversi kode dari satu format ke  format  lain  ➤ Biner ke BCD  (Binary Coded Decimal)  ➤ BCD ke Seven Segmen                       ➤  BCD ke Grey Code                              ➤  Grey Code ke BCD                              ➤ BCD ke  Excess-3                                ➤  Excess-3  ke BCD                ...

Skematik dan PCB Layout Rangkaian Adaptor (Power Supply) AC to DC output 5 Volt

Software Proteus 8 Professional merupakan salah satu software elektronik yang digunakan untuk membantu para designer dalam merancang dan mensimulasikan suatu rangkaian elektronik. Software ini memiliki dua fungsi sekaligus dalam satu paket, yaitu sebagai software untuk menggambar skematik dan digunakan sebagai merancang gambar Printed Circuit Board (PCB). Pada tulisan kali ini saya akan memberikan sedikit tutorial cara membuat rangkaian Adaptor (Power Supply) AC to DC untuk keluaran tegangan 5 volt. Aplikasi yang akan digunakan disini adalah Proteus 8 Profesional. Alasan saya menggunakan aplikasi ini karena inilah salah satu aplikasi paling popular digunakan para desainer. Selain itu aplikasi ini juga mudah didapat dan kompatibel dengan banyak platform. Sedangkan alasan saya mengangkat tema ini karena ini juga salah satu tugas mata kuliah saya di semester 4, yaitu mata kuliah Elektronika Dasar. Di mata kuliah ini banyak dijelaskan bagaimana membuat rangkaian elektronika dan praktik pem...

Studi Peralatan Pembangkit dan Penggerak Mula

Gangguan pada Pusat-pusat Listrik secara garis besar dapat dibagi atas 4 kelompok, yaitu : a. Gangguan pada sirkit listrik generator b. Gangguan pada mesin penggerak mula c. Gangguan pada instalasi yang berhubungan dengan lingkungan seperti instalasi air pendingin dan saluran air terbuka pada PLTA . d. Gangguan pada sirkit kontrol . Dalam instalasi yang dijaga oleh operator seperti Pusat Listrik dan Gardu Induk ada gangguan yang tidak atau belum dilihat oleh Relai , tapi dilihat oleh operator yang kemudian berinisiatif men-trip-kan atau membuka Pemutus Tenaga ( PMT )/ circuit breaker demi keselamatan instalasi , maka dalam hal ini operator bertindak sebagai relai. Gangguan pada Sirkit Listrik Generator yang menyebabkan tripnya PMT, pada umumnya disebabkan oleh : a. Gangguan diluar seksi generator tetapi PMT generator ikut trip sebagai akibat kurang selektifnya relai generator b. Ada gangguan dalam seksi generator yang disebabkan karena: " Kerusakan generator atau alat ...